Testing Intervals

How often an electrical appliance needs to be tested varies according to the workplace and the type of environment within that particular workplace. In practice that means anywhere between every 3 months and every 5 years.

The interval table

This is the schedule we work to. Find the row that describes your workplace — if two look close, call us and we will confirm which applies.

Intervals between inspection and testing, per AS/NZS 3760.
Type of environment or equipmentEquipment, cord sets, cord extension sets and EPODsRCD push-button test — portableRCD push-button test — fixedRCD operating time — portableRCD operating time — fixed
Factories, workshops, places of manufacture, assembly, maintenance or fabrication6 monthsDaily, or before every use, whichever is longer6 months12 months12 months
Environment where the equipment or supply cord is subject to flexing in normal use, or is open to abuse, or is in a hostile environment12 months3 months6 months12 months12 months
Environment where the equipment or supply cord is not subject to flexing in normal use, is not open to abuse and is not in a hostile environment5 years3 months6 months2 years2 years
Residential type areas of hotels, residential institutions, motels, boarding houses, halls, hostels and accommodation houses2 years6 months6 months2 years2 years
Equipment used for commercial cleaning6 monthsDaily, or before every use, whichever is longerN/A6 monthsN/A
Hire equipment — inspectionPrior to hireIncluding push-button test by hirer prior to hireN/AN/A
Hire equipment — test and tag3 monthsN/A3 months12 months
Construction work3 monthsDaily, or before every use, whichever is longerN/A3 monthsN/A

Transcribed from AS/NZS 3760. Where a workplace falls under more than one row, the shorter interval applies.

The short version

  • Every 3 months — construction work sites, which are classified as a hostile work environment.
  • Every 6 months — factories, workshops and places of manufacture, maintenance or fabrication, and equipment used for commercial cleaning.
  • Every 12 months — where the equipment or its supply cord is subject to flexing, open to abuse, or in a hostile environment.
  • Every 5 years — low-risk environments where the cord is not flexed, not open to abuse and not in a hostile environment. Most offices sit here.

RCDs are on a separate schedule

Residual current devices need both a push-button test and a measured operating-time test, at different intervals — see the last four columns above, and our RCD testing page.

Hire equipment

Hire equipment is inspected prior to every hire, including a push-button test by the hirer, and is tested and tagged every 3 months.

The standard we work to

Elite Test and Tag refers to AS/NZS 3760 for testing frequency. We test to the edition current at the time of your job.